Configuration and CFG-300 LCD Service Tool
58
Remote Annunciator
Troubles related to the annunciator can have two possibilities: either the main panel and annunciator failed to
communicate with each other, or an un-configured remote annunciator is responding to the main panel. In both the
cases, the following trouble message is displayed:
Four-wire smoke detector supply
The four-wire smoke detector supply is supervised for shorts. When a short is detected on a four-wire smoke supply
the power is cut off and a trouble message is generated. Press the system “RESET” key to restore the power the
system. If the short is removed, the panel will return to normal; otherwise the trouble message will stay.
Note: The trouble code and info is for trained service personnel only.
RAU num mismatch
trouble 1/ 1
Trb:0x03 Info:0x0001
11:45 SAT 2003-02-03
Trouble Type
EVENT
01 of 09
DATE
TIME
"INFO" Key
Trouble code
Trouble info
"INFO" Key
4Wire Pwr. Supply
short 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info