FA-300-6L Installation and Operation Manual
29
Figure 19: Evacuation and Alert Codes
Single Stage Operation
In a single stage system all alarm inputs are treated in a similar manner. Alarm inputs include any of the following:
Non-Verified Alarm, Verified Alarm, Sprinkler Alarm, Water flow Alarm, and General Alarm Circuits. If any of these
alarm inputs occur when the panel is not already in alarm, the following occurs:
The Buzzer sounds steadily
If Fire Drill is active, it is cancelled
The Common Alarm Indicator turns on
The Common Alarm, Auxiliary Alarm and all correlated relays will activate if Aux Disconnect is not active
The Auto Signal Silence Timer, if configured, starts
The Signal Silence Inhibit Timer, if configured, starts
All connected relays programmed to the input are activated (provided that Aux Disconnect is not active)
Non-disconnected strobes associated with the input are activated
Non-disconnected signals associated with the input are activated at the evacuation rate
Subsequent alarms when the panel is already in alarm cause the following:
The alert buzzer sounds steadily
If Signals have been silenced as a result of the Signal Silence button or the Auto Signal Silence Timer, Signals
are resounded as they were before Signal Silence, the Signal Silence Indicator is turned off, and the Auto
Signal Silence Timer, if configured, is restarted
Any additional non-disconnected strobes associated with the new input are activated continuously
Any additional non-disconnected signals associated with the new input are activated at the evacuation rate
0.5s
0
.
5
s
1.5s
0.5s
0
.
5
s
5s 10s
CONTINOUS
TEMPORAL CODE
MARCH CODE
CALIFORNIA CODE
0.5s
2.5s
ALERT CODE