Functional Setup
3.2 DIP Switches
There is one bank of DIP switches to be set. DSW1 is found at the top left hand corner and is
used to select the smart relay address. Valid addresses are 1 to 6 inclusive, for FA-300 Series
and FR-320 Series Fire Alarm Panels; 1 to 7 inclusive for FX-350/351 and FX-3500/FX-
3500RCU Series. Set address as described in 3.2.1 Dip Switch DSW1-1 to 1-3.
3.2.1 Dip Switch DSW1-1 to 1-3
3.2.2 Dip Switch DSW1-4
Used to disable the Auxiliary Disconnect function from the Fire Alarm Panel.
Attention: Dip Switch DSW 1-6 and DSW 1-8 are always to be set to OFF.
Table 2 SRM-312 DIP Switch Address Setup
Address DSW1-1 DSW1-2 DSW1-3
1ONOFFOFF
2OFFONOFF
3ONONOFF
4OFFOFFON
5ONOFFON
6OFFONON
7
(FX-350/351
and
FX-3500/3500RCU)
ON ON ON
Table 3 Enable or Disable Auxiliary Disconnect Function
DSW1-4 Position Function
ON Enable auxiliary disconnect function from the fire alarm panel.
OFF Disable auxiliary disconnect function from the fire alarm panel (Aux. disconnect
will not disconnect these twelve relays). This is the default setting. The DSCNN
(Aux Disconnect) LED is not active when Aux Disconnect is active on the Fire
Alarm Control Panel in this mode.
!